The Difference Between Neutral and Earth Ground in AC Installations
If you’ve ever had the pleasure of upgrading old electrical wiring in a residence, you know that a separate earth ground wire was generally not used in the past. In such cases, you find yourself with 2 wires: live, and neutral.
Now, you might want to install a grounded outlet without redoing a lot of wiring. A common method of getting around this little problem is to install the new 3-conductor outlet by tying live to one prong, neutral to the other prong, and then using a jumper wire to connect neutral to the ground connection inside the outlet.
“Theoretically, this should work just fine!” you reason.
It turns out that theoretically, you are in fact correct. Practically speaking, adding a “ground” in a 2-wire installation by tying neutral and ground together has several serious – and possibly dangerous – drawbacks.
Here’s the scoop.
This here post assumes that you actually have some idea of how AC power systems work. Obviously, if you know very little about AC wiring and power distribution systems, you need to do some serious homework first before you get yourself killed. You can check out the following links:
Alrighty, now that that’s out of the way, here’s the deal. In a standard AC electrical scheme, there is a generator that spits out 3 phases of AC. Those phases are then fed to transformers, through high-voltage power lines over vast distances, through another local transformer to step down the voltage, and then into the main panel in your home. From there, you have wiring to your power outlets. Simple enough, yes?
Right. So there you are, and you have an old 2-wire system. Maybe in your main panel, you don’t even have circuit breakers – you might have fuses if your system is really old. Alternatively, if a bonehead electrician rewired your place at some point, you might have breakers and still have 2-conductor wiring everywhere. If your electrician is really bad, you could even have differential circuit breakers with no ground wires anywhere.
A differential breaker, or Ground Fault Circuit Interrupter (GFCI), uses an inductor to “measure” the current flowing through both the neutral and live wires. Normally, the currents flowing through both wires will be equal, and thus all is well. If, however, there is an equipment failure and/or live is shorted to ground through a human body, then obviously the currents through live and neutral will not be equal. At that point, the current imbalance (i.e. the current differential) trips the breaker, and power is cut. Since the trip current for such breakers is typically 30mA, and it takes somewhere around 200mA to stop a human heart, you can go ahead and drop your hairdryer into the bathtub with you and you won’t die. Sweet!
Okay, now comes the reason why using neutral as ground is NOT the best idea. The following is a typical electrical hookup:
Note that in our example, the house in question is connected to all 3 phases from the power company. This 3-phase setup is rare in highly populated areas – but quite common in rural areas in many countries! In single-phase setups, one house will be connected to Phase 1 from the transformer, the next house will be connected to Phase 2, and a third house will be connected to Phase 3, and all the houses will share the neutral line. Neutral is tied to ground because as the “common return point” for all three phases, the net voltage/current at that point is ideally zero. This is easy enough to see if you draw three sine waves, each 120° out of phase with each other, and add them together (see the homework links above for more info).
In any case, what happens when there is a fault in the gizmo? Let’s say that a fault occurs such that the live wire going into the electric gizmo is shorted to its metal casing. Since the metal casing is grounded, the fault current is shunted to ground as follows (look for the red dots):
Here we see that the current is shunted to ground. When this happens, the differential breaker in the main panel detects that the current on the live is higher than the current coming back on the neutral wire. Thus, the breaker trips, and both live and neutral are cut off before anyone dies. This is a good thing.
All right – so what happens when we have 2-conductor wiring, and we connect ground and neutral at the power outlet for our Gizmo? See below:
Now things might begin to become a bit more clear. In this case, when the Gizmo has a fault condition and current is shorted from live to the “grounded” casing, ground = neutral since we tied those two lines together in the power outlet! Thus, the circuit is not broken because even if we have a differential breaker in the main panel, it will not trip since everything seems well as far as the breaker is concerned. That’s bad.
Of course, if the failed Gizmo draws too much current, the fuse or normal breaker in the main panel will blow/trip – but we’ve lost the protection from electrocution provided by the differential breaker, which is kind of important.
Note that under normal conditions, the casing IS actually connected to ground in this case – via the neutral line back to the transformer. In the USA, neutral is also tied to ground at the main panel in each home. Still, if you look again at the diagram above, that does nothing to improve the situation.
You may be wondering what the fuss is all about. After all, assuming that all is well, the neutral-connected Gizmo casing will not electrocute you since you would actually have to be grounded in order for any current to flow through you. Furthermore, even if you ARE grounded, your body would probably present a higher impedance path to ground than the neutral line that runs back to the transformer where it is connected to an actual earth ground. As we know, electrons will always seek the path of least resistance since they are, in a word, lazy. And, as I already mentioned, neutral is basically “zero” current/voltage since the neutrals of all phases are connected together with earth ground. So, what’s the big deal?
Well, you kind of have a point – theoretically speaking. The problem comes when all is not well. You cannot rely on the neutral staying connected to all three phases. A separate earth ground provides an added layer of protection under severe fault conditions even if the above theoretical scenario is true. For example, if neutral is temporarily disconnected for some reason – either in your house or at the electric company’s equipment – you’ve got a problem. In fact, you’ve got a seriously big problem because at that point, power surge conditions can cause pretty big problems. When your Gizmos start to explode due to power spikes as a result of load imbalances in the 3-phase system, and there is no ground to save you, you’re in big trouble.
Granted, there are other safety systems in place. Granted, the aforementioned severe fault condition should be almost nonexistent in a well-maintained electrical system. But that brings up the whole point of a separate ground: safety! By connecting neutral and ground at the outlet, at the very least you are effectively disabling any human safety mechanisms present in the electrical installation in your home. At worst, you are asking for disaster – rare though such occurrences may be.
So, if you want to play it safe (and you do!), add a ground line to your 2-wire setup instead of connecting neutral and ground. Install differential circuit breakers for your own protection.
Theory is good, but practicality and safety is better.
No related posts.





WELL WRITTEN TUTORIAL ON ELECTRICAL SAFETY
Hi,
I hope you can help me with my CVT’s (constant voltage transformer) earth/neutral connection. The input to CVT requires the earth to be connected to the body. In the CVT’s output – the earth is tied to neutral. Effectively, only two wires, i.e. live and neutral connects to my audio power amplifier.
Since my audio power amplifier requires earth/ground connection, I then connected the earth pin of my amplifier to the house earth wire which runs into the ground separately.
Recently, a EE friend of mine asked me to remove the ground from the neutral at the CVT output level.
Are there any advantages by connection earth and neutral in relation to EMI?
Thank you.
Tony
Not that I know of. Generally speaking, an actual earth ground is best for EMI shielding. The closer the earth connection is to the device, the better. Then again, EMI is not exactly my specialty, so I could be wrong!
Thanks for the reply. Unfortunately, if I remove the earth from the neutral my tester says ” No earth”. My electrician says there”s nothing wrong with the wiring but couldn’t explain why tester shows no earth.
The manufacturer emailed me this “Leaving the neutral to earth link in place is fine. It provides a zero volt reference for the output neutral. If you were to disconnect it, the output neutral would float at around 100V to 120V with respect to earth. Most people have the output neutral earthed.”
Not sure what should be the correct method. I asked my electrician to install another rod to the ground and connect that to the neutral of the CVT. At least now the tester says everything is normal.
Tony
hey scottie i somehow lost the neutral to my light fixture and used the ground instead of the neutral and the light works fine is this dangerous i would have to do a lot of cutting and patching to fix this correctly which i would like to avoid thanks
Theoretically, it will work, yes. But practically speaking, it’s a bad idea.
If your light was/is ever protected by a differential breaker (GFCI), it will trip a lot. In fact, you probably don’t have that lighting circuit protected with a GFCI breaker, because if you did, it should trip the instant you turn the light on. If it’s NOT tripping, then something is seriously wrong.
While it is true that neutral is tied to ground at different points in the grid depending on what country you live in, neutral is not ground for all practical purposes. Neutral is the “return line” for the AC, which means that theoretically, since all the neutral lines of the larger 3-phase power grid are tied together, neutral will basically be 0. But in practice, no grid is perfectly balanced, so it’s not 0. By using the ground as a neutral, you are essentially risking an energized ground, which defeats the actual purpose of the ground in your whole house. Neutral isn’t really “neutral”. By using the ground as a return, you are also counting on the earth’s impedance between your installation and the nearest neutral/gnd tie to remain constantly low, which of course it doesn’t, and instead depends on things like soil humidity and type.
In short, you might be able to get away with it, but it could result in big headaches and possibly even a shock hazard down the road. Better to go the cutting and patching route if you ask me!
What if i connect the ground terminal to the wall of my house? My house is grounded anyway. will that work.
Well, usually every outlet in the house is connected to the same ground point, that being a conducting rod driven into the ground. The composition and length of the rod will vary based on the type of soil, humidity, etc. in your area. If you have multiple ground points – even if they are only on opposite sides of your house, you can experience the very interesting problem of ground loops. Essentially, with 2 grounding points, there is no way to ensure that the potential of the earth at those two points is always the same. So, under certain conditions, you can have problems with electrical gizmos breaking or acting strangely because ground is no longer ground… or because ground on one side of the house is not the same as ground on the other.
The other thing is that grounding to your house may work, but it depends on what your house is made of, if the conductivity of the walls changes too much depending on temperature and humidity, and so on. So, the best option is to have 1 real grounding rod, and connecting everything to that 1 point. Other stuff MAY work, but it also may cause you headaches down the road.
I wonder if you can help. I’m in Spain, near Barcelona, where we use the 2-pin Schuko type plugs. Most of my electrical stuff is 3-pin UK wired and I use an adapter with an earth on it as the Shuko plugs have an earth pin (whether it does anything is another matter, how would I know???)
I am getting minor electrical shocks from my electrical devices when plugged in to all but a couple of the sockets. I imagine that neutral is not properly earthed. I also imagine that if I DO earth neutral the fuses will blow – there’s usually a reason why neutral is not properly earthed. My landladies are tight and will not pay for an electrician – much less pay for the place to be re-wired. We can’t even change the electricity bill into our name because it will require a safety certificate (which it doesn’t have and which no electrician would sign off meaning they would need to re-wire).
Is there a device you know of that I can plug in between my 4-way adapters and the offending power sockets to act as an earth? Even if I have to physically take a wire and attach it to a grounding rod, that would be better than getting current through the USB sockets on my laptop
So, do the outlets in the wall look like one of these: http://en.wikipedia.org/wiki/Schuko ??
If there are either the ground tabs, or the actual ground prong in the wall sockets, then ground should work – unless it isn’t wired properly inside the apartment. Some plug adapters don’t actually have a real ground prong – it’s just plastic. That’s bad juju. The other possibility is that the sockets are wired incorrectly, although that shouldn’t really cause a shock hazard if the ground is connected properly.
Assuming that your socket adapter is not goofy somehow, then it sounds like the wiring was not done properly. You could investigate and cut the power to one of the outlets at the breaker panel, and then remove the cover plate on the outlet and see if the ground prong/tab is even wired up. Sometimes in old buildings, owners will save money by removing old 2-wire (phase/neutral) lines and install grounded outlets without actually connecting the ground up to anything because they don’t want to pay an electrician to rewire everything. That’s seriously “illegal” according to the electrical codes of most EU countries, but then again in certain countries, you don’t actually HAVE to fix the wiring if the house/building is a certain age. It’s all kind of ridiculous, actually.
Worst case, you could run your own ground wire through a window or something and attach it to a grounding rod in the earth, but get a book or something on how to do it properly. The length of the rod, type of metal, diameter, average humidity level of the soil, etc. are all kind of important for a really good ground.
Hope this helps!
@Simon Brown
I have the same problem. I get a minor shock from my Aluminum Apple keyboard. I always have to wear slippers when using the computer. just like you I bought my mac from USA with 3 prong connections but in my country we have 2 prong connections.
Another idea would be to connect a power strip to the 2-prong outlet. Then, connect a wire to one of the ground prongs in the power strip to a bare copper cold water pipe. Generally speaking, water pipes act as an adequate ground. There’s no guarantee it will work well, and it requires that all pipes are conductive metal and not plastic somewhere in the building, but it might help. Oh, and one other thing: if with a 2-prong plug zaps you a bit, unplug it, and replug it the other way around (so that the prongs of the plug are in the opposite hole they were in before). That works well for things like metal touch lamps and such that give you a little “buzz” when you touch them.
@Scottie
Thank you so much for your help.
I tried the “plug it in the other way up” and still got shocks. I guess that means that neutral isn’t properly earthed on that spur. Spain is all done with spurs apparently – rather than loops like what they do in the UK.
From memory the power strips I’m using (which also contain surge protection) can be dismantled and I can solder in a wire to the earth – it will look a bit dodgy but don’t care – at least if I attach it to the central heating pipes I shouldn’t get shocks…
is it OK to short Neutral and Earth bus bar in the Distribution Panel?????
I think in the US, neutral is often tied to ground at the breaker panel. In Europe, it usually is not. I usually just go with whatever the local wiring standards indicate.
This article really helped me out. It is written so well! Thanks a lot mate.